Pacific X-Ray Barrier Door Set Installation

 

This tool is designed to filter the available results as you search. Once you have applied a filter, you may need to reset the filter to be able to see all other available options.

 

Please note:  Hardware is not included with our doors. However, we are pleased to help in sourcing high-quality hardware from ASSA ABLOY at an additional cost.

For BPIR Documents related to ASSA ABLOY hardware, please see: ASSA ABLOY 

For hardware from other suppliers, please refer to the individual hardware supplier for information.

 

To see our installation videos please click here.

Installation wall framing requirements

Pacific X-Ray Barrier Door Set

WALL TYPE: Timber stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Lead Shielding:

  • Detail shown for lead thickness up to 2mm thick. NOTE Lead shielding above 2mm is possible, however special details are required. If required please contact Pacific Doors customer services.

Fasteners:

  • Frame screwed to stud through timber packing.
  • Frame to be screw fixed (10g x 50mm self tapping) at 600mm nominal centres. Two fasteners per location where applicable.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required
  • Wedging Gap:
  • 0-15mm
H-D-XRAY-S-T-D image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Lead Shielding:

  • Detail shown for lead thickness up to 2mm thick. NOTE Lead shielding above 2mm is possible, however special details are required. If required please contact Pacific Doors customer services.

Fasteners:

  • Frame screwed to stud through timber packing.
  • Frame to be screw fixed (10g x 50mm self tapping) at 600mm nominal centres. Two fasteners per location where applicable.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging Gap:

  • 10mm
H-D-XRAY-S-T-D2 image
WALL TYPE: Masonry
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Jamb fixing at 600mm nominal centres
  • Expansion anchors eg. M10 countersunk 'Ramset' Dynabolts
  • M12 countersunk masonry screwbolts

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging Gap:

  • 0-15mm
H-D-XRAY-S-M image
WALL TYPE: Steel stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Lead Shielding:

  • Detail shown for lead thickness up to 2mm thick. NOTE Lead shielding above 2mm is possible, however special details are required. If required please contact Pacific Doors customer services.

Fasteners:

  • Frame screwed to boxed stud at 600mm nominal centres with self tapping screws.
  • Steel studs may be riveted (steel pop rivets) or screwed (9g x 45mm self tapping) to the frame bracing straps.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging Gap:

  • 0-15mm
H-D-XRAY-S-S image