Installation wall framing requirements

Pacific VP30HR Double Action Timber Framed Door Set -/30/30

WALL TYPE: Timber stud
FRAME TYPE: Timber

Frame materials available:

  • Radiata pine or denser (standard thickness is 30mm)

Fasteners:

  • Frame - Either nailed (75 x 3.2mm) or screwed (10g x 75mm) at 600mm centres. Two fixings per location.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.
  • Pryda Jamb-fixa brackets Type JFB100 at 500mm centres may be used to fix profiles A & B to approved walls.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • ex75 x 50mm minimum.

Wedging gap:

  • 0-10mm
F-D-VP30DA-T-T-1 image
WALL TYPE: Masonry
FRAME TYPE: Timber

Frame materials available:

  • Radiata pine or denser (standard thickness is 30mm)

Fasteners:

  • Frame - M8 or M10 'Ramset' Dynabolts at 600mm centres and near hinges. Fixings on or near centre of frame jamb.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging gap:

  • 0-15mm
F-D-VP30DA-T-M-1 image
WALL TYPE: Steel stud
FRAME TYPE: Timber

Frame materials available:

  • Radiata pine or denser (standard thickness is 30mm)

Fasteners:

  • Frame - Screwed (10g self tapping) at 600mm min. centres. Minimum of one screw per location. Frames may also be installed by screw fixing the steel studs to the back of the timber frame during wall construction.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • 65 x 34mm minimum of 0.55 MSG gauge.

Wedging gap:

  • 0-10mm
F-D-VP30DA-T-S-1 image