Pacific VP120-S Sliding Fire Door Set -/120/30

 

The VP120-S is a Pyropanel FR board door.

The VP120-S sliding fire door set is used where a large opening in a fire separation (up to 10m2) is required to be closed off in the event of a fire and/or in daily use.

The slider may be concealed behind an appropriate cavity wall. Automatic opening and closing is not currently available for Sliding Fire Doors. 

The VP120-S is a sliding fire door set. The door leaf can be faced in plywood or steel sheet, and is capped with steel channel to 4 edges and hung from a sliding track system.

A counterweight system, released by a fusible link or electromagnetic hold open devices that are linked to a fire detection system, closes the door leaf in the event of a fire.

For higher fire ratings and larger sized doors refer to the VP240-S slider.

VP120-S is not available as a smoke control door set.

This door type is suitable for interior installation only.

The thickness of the VP120-S door leaf is 65mm with an approximate leaf weight of at least 31kg/m2

 Wall Type Fire Resistance Rating
Stability/Integrity/Insulation
Door Application Max Leaf
Height (mm)
Max Leaf
Width (mm)
 Timber Stud Wall
Masonry Wall
 -/120/30 Single 4000 3000

Notes:

  1. The VP120-S is not available as a ‘pair’ door set. Refer to the VP240-S
  2. The maximum area per sliding door leaf is 10.5m2

Product Options

Leaf Facings

  • Plywood
  • Steel Sheet 0.9mm

Leaf Edges

The leaf edges listed below are available for the VP120-S door set

Hardware/Closing Systems

A Standard Track System is supplied with this door set.

Standard Closer

Weight and pulley system with self-closure activated by fusible link in the event of fire.

Electromagnetic Closing Weight System

A weight and pulley system modified for electromagnetic release is available. Closure is on fire/smoke detection activated by sensors (by others) mounted each side of the door set to lintel or ceiling.

Frame Types & Profiles

Please refer to the installation instructions for this door set for more information.

Meeting Stiles

Not applicable for this door set.

Wall Types

Masonry

The VP Slider may be hung from a concrete or masonry wall either of precast concrete (thickness 100mm minimum) or grouted blockwork (thickness 190mm minimum).

Drywalls

Special wall construction is required for mounting on plasterboard walls. Please contact Pacific Doors for further information.

Product Optional Extras

Vision Panels

Please contact PDS for information on vision panel options.

Sidelights and Overlights

Not applicable for this door set.

Overpanels

Not applicable for this door set.

Additional Door Options

Cavity Wall System

Thermal Insulation

This door leaf has a thermal insulation rating (R-value) of 0.692 Km2/W.

Building Product Information Statement