Installation wall framing requirements

Fire Rated Interconnecting Doors

WALL TYPE: Timber stud
FRAME TYPE: Timber

Frame materials available:

  • Hardwood timber - Min. density 580kg/m≥ (minimum thickness is 30mm)

Fasteners:

  • Frame - Either nailed (75 x 3.2mm) or screwed (10g x 75mm) at 600mm centres nominal. Two fixings per location.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.
  • Pryda Jamb-fixa brackets Type JFB100 at 500mm centres may be used to fix profiles A & B to approved walls.

Stud size:

  • Ex 100 x 50 minimum.

Wedging gap:

  • 0-10mm
A-D-SPA40FR60-TC-T image
WALL TYPE: Timber stud
FRAME TYPE: Timber

Frame materials available:

  • Hardwood timber - Min. density 580kg/m≥ (minimum thickness is 30mm)

Fasteners:

  • Frame - Either nailed (75 x 3.2mm) or screwed (10g x 75mm) at 600mm centres nominal. Two fixings per location.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.
  • Pryda Jamb-fixa brackets Type JFB100 at 500mm centres may be used to fix to approved walls.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • Ex100 x 50 minimum.

Wedging gap:

  • 0-10mm
A-D-SPA40FR60-TS-T image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Frame to be screw fixed (10g self tapping) at 600mm centres nominal. Two fasteners per location where applicable.

Head Fixing (minimum)

  • Single door - none required
  • Paired door - single central fixing required

Stud Size:

  • Ex 100 x50 minimum

Wedging gap:

  • 0-10mm
A-D-SPA40FR60-SC-T image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Frame to be screw fixed (10g self tapping) at 600mm centres nominal. Two fasteners per location where applicable.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Stud size:

  • Ex 100x50 minimum.

Wedging gap:

  • 0-10mm
A-D-SPA40FR60-SS-T image
WALL TYPE: Masonry
FRAME TYPE: Timber

Frame materials available:

  • Hardwood timber - Min. density 580kg/m≥ (minimum thickness is 30mm)

Fasteners:

  • Frame - M8 or M10 'Ramset' Dynabolts at 600mm centres nominal. Fixings on or near centre of frame jamb.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging gap:

  • 0-15mm
A-D-SPA40FR60-TC-M image
WALL TYPE: Masonry
FRAME TYPE: Timber

Frame materials available:

  • Hardwood timber - Min. density 580kg/m≥ (minimum thickness is 30mm)

Fasteners:

  • Frame - M8 or M10 'Ramset' Dynabolts at 600mm centres nominal. Fixings on or near centre of frame jamb.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging gap:

  • 0-15mm
A-D-SPA40FR60-TS-M image
WALL TYPE: Masonry
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Jamb fixing at 600mm centres nominal
  • Expansion anchors eg. M10 countersunk 'Ramset' Dynabolts
  • M12 countersunk masonry screwbolts

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging gap:

  • 0-10mm
A-D-SPA40FR60-SC-M image
WALL TYPE: Masonry
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Jamb fixing at 600mm centres nominal
  • Expansion anchors eg. M10 countersunk 'Ramset' Dynabolts
  • M12 countersunk masonry screwbolts

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging Gap:

  • 0-10mm
A-D-SPA40FR60-SS-M image
WALL TYPE: Steel stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Frame screwed to boxed stud at 600mm centres nominal with self tapping screws.
  • Steel studs may be riveted (steel pop rivets) or screwed (9g x 45mm self tapping) to the frame bracing straps.

Head Fixing (minimum):

  • Single Door - none required
  • Paired door - single central fastener required

Stud size:

92 x 34mm minimum of 0.55 SMG gauge

Wedging gap:

  • 0-10mm